Description
Features |
Wireless high-voltage voltage and induced voltage measurement, high-voltage electrical inspection |
power supply
|
Receiver: DC7.5V, 5 AA alkaline batteries |
|
Detector: Zinc-manganese dry battery 6F22, 9V |
Transmission distance |
Wireless transmission, straight-line transmission distance of about 30 meters |
Electrical inspection level |
70V~220kV (110V, 220V, 3kV, 6.3kV, 10kV, 35kV, 66kV, 110kV, 220kV) |
Display range of ground voltage |
0.1kV~120kV (voltage to ground) |
Display accuracy of ground voltage |
High-voltage overhead line ±15%±5dgt (other applications: ±25%±5dgt) |
Line voltage display range |
0.1kV~220kV (corresponding display line voltage, multiply √3 according to the ground voltage) |
Line voltage display accuracy |
High-voltage overhead line ±15%±5dgt (other applications: ±25%±5dgt) |
Probe diameter |
Φ70mm |
Probe length |
55mm |
Radio frequency |
315MHz |
Display mode |
3.5 inch color screen |
LCD size |
72mm×55mm |
Power indicator |
The detector has a green power indicator |
Electric inspection instructions |
The detector has sound and light indication function, red double flashing light indication and “beep-beep-beep” buzzer during electricity inspection |
Display rate |
2 times/sec |
Data storage |
500 groups (power failure or battery replacement will not lose data) |
LCD backlight |
Have |
Automatic shut-down |
After about 15 minutes of power on, the meter will automatically shut down |
Battery voltage |
The battery voltage is insufficient, and the low battery symbol ” ” is displayed |
Power consumption |
Detector: 70mA Max; Receiver: 200mA Max |
Instrument quality
|
Receiver: 450g (including battery); |
|
Detector: 450g (including hook battery); |
Instrument size |
Receiver: 187×119×48mm; Detector: 146×100mm×75mm |
Insulation rod length |
Maximum diameter Φ38mm; length: 3 meters |
Insulation test
|
Both ends of the insulating rod after stretching: AC 220kV/rms |
|
Receiver and detector: AC3700V/rms (between exposed metal and plastic case) |
outside interference |
No strong electromagnetic field; there should be no 315MHz co-channel interference at the test site |
Working temperature and humidity |
-10℃~40℃; below 80%rh |
Storage temperature and humidity |
-10℃~60℃; below 70%rh |
Give a Review