Description
Features |
Frequency measurement, phase measurement, phase sequence display, voltage measurement, voltage inspection |
|
power supply |
Host: DC7.5V, 5 AA alkaline batteries Detector: zinc-manganese dry battery 6F22, 9V |
|
Baseline conditions |
23℃±5℃, below 75%rh |
|
Phasing |
Contact phasing: The bare wire below 35kV or the wire with insulating sheath below 550kV can contact the wire core phase non-contact phasing. When the bare line voltage exceeds 35kV, a non-contact test must be used, and the probe is gradually approached to the core phase of the conductor |
|
Transmission distance |
Wireless transmission, straight-line transmission distance of about 30 meters |
|
Differential characterization |
In-phase: -30°~30° |
Out-of-phase: 90°~150° and 210°~270° |
Phasing voltage |
70V~550kV |
|
Phase range |
0.0°~360.0°; Accuracy: ≤±12°; Resolution: 0.1° |
|
Frequency range |
45.0Hz~65.0Hz; Accuracy: ≤±2Hz; Resolution: 0.1Hz |
|
*Voltage range |
70V~110kV; Accuracy: ±15%±5dgt Resolution: 100V |
|
*Voltage accuracy |
High-voltage overhead line ±15%±5dgt (other applications: ±25%±5dgt) |
|
transmit frequency |
433MHz, 315MHz |
|
display mode |
3.5 inch color screen |
|
LCD display size |
72mm×55mm |
|
Meter size
|
Host 187×119×48mm |
|
Detector |
146×100mm |
|
Phase indication |
Simultaneous display of phasor diagram and numbers |
|
Work instructions |
When phase checking, the detector has sound and light indication function, red double flashing light indication and “beep-beep-beep” beep |
|
data storage |
100 groups, flashing “FULL” symbol indicates that the storage is full |
|
Data access |
Data access function: “READ” symbol display |
|
Power consumption
|
Detector: 70mA Max Max |
|
Host |
: 150mA Max |
|
Instrument quality
|
Detector: about 250g (including hook and battery) |
|
Host |
: about 450g (including battery) |
|
battery voltage |
The battery voltage is insufficient, and the low battery symbol ” ” is displayed |
|
Automatic shut-down |
The meter shuts down after 15 minutes of inactivity |
|
Insulation rod length |
Maximum diameter Φ38mm; Length: 800mm in contracted state; 3015mm in extended state |
|
Insulation test |
Both ends of the insulating rod after stretching: AC 220kV/rms; host and detector: AC3700V/rms (between exposed metal and plastic casing) |
|
Suitable for safety regulations |
GB13398-92, GB311.1-311.6-8, 3DL408-91 standards and the newly promulgated national electric power industry standard “General Specifications DL/T971-2005 for 1kV ~ 35kV Portable Phase checking Apparatus for Live Work” |
|
Voltage Test Function |
NO |